Skip to main content

Hopewind HSHV385K-G01

385 kW Grid-tie Three-phase
Datasheet PDF
Rated AC (kW)
385.00
Strong · top 1%
Euro eff. (%)
98.7
Typical · median 98.5%
MPPT
8
Typical · median 8
Max DC (V)
1500
Strong · top 23%
Weight (kg)
142.0
Strong · top 7%
Warranty (yrs)
-
Not published

The HSHV320/330/350/385K-G01 series comprises utility-scale string inverters engineered for large-scale solar farms, where reliability under harsh conditions and maximum energy harvest from every string are essential. Built on advanced SiC technology, these units deliver high efficiency while reducing thermal losses and extending the lifespan of power electronics. A key advantage is the 8 independent MPPTs rated up to 60A each, allowing flexible configuration for modules with different characteristics and uneven irradiance conditions typical of expansive ground-mounted installations. An intelligent I-V scanning system automatically detects abnormal strings, simplifying maintenance and reducing downtime. The IP66-rated enclosure with optional C5 anti-corrosion protection enables operation in industrial, coastal, and desert environments, while full power output is maintained even at ambient temperatures of 45 degrees Celsius. The inverter supports SVG function and weak-grid (SCR) adaptability, improving grid connection stability. Wi-Fi/PLC communication and compatibility with aluminum cables up to 400mm2 help lower installation and wiring costs. PID recovery functionality and surge protection minimize module degradation risk, contributing to stable LCOE throughout the system's operating life.

Ranking

238 inverters from 100 to 500 kW
Metric This inverter Median Position in class Rank in class
European efficiency 98.7% 98.5% Typical 43
MPPT trackers 8 8 Typical 82
Max DC input voltage 1500 V 1100 V Strong · top 23% 1
Weight per kW 0.4 0.7 Strong · top 7% 16
Warranty - 5 yrs Not published -
Colour key Strong - top 25% Typical - middle 50% Weak - bottom 25%

Specifications

Open datasheet PDF
Rated AC power 385 kW Continuous output
Phases Three-phase
Nominal AC voltage 800 V 640~920 V
Max AC current 277.9 A
Grid frequency 50 Hz
Power factor 0.8 leading~0.8 lagging
Harmonic distortion (THD) 3.0 %
Max DC voltage 1500 V Caps the string length
MPPT voltage range 500 to 1500 V
Start-up voltage 550 V
MPPT trackers 8 4 strings each
Max input current per MPPT 60.0 A Must exceed the panel's Imp
Max short-circuit current per MPPT 90.0 A Must exceed the panel's Isc
European efficiency 98.7 % Weighted across part loads
Max efficiency 99.0 % Best single operating point
Dimensions 919 × 1135 × 416 mm Height × width × depth
Weight 142.0 kg 0.4 kg per kW
Enclosure IP66
Cooling forced-air
Operating temperature -25 to 60 °C
Max altitude 4000 m
Interfaces Wi-FiDisplay
Protocols RS485PLCWi-Fi
Protection AFCIDC switchSurge protection
Certifications IEC 62109IEC 61000IEC 61727IEC 62116IEC 60068IEC 61683EN 62920IEC 63027EN 50530EN 50549-1EN 50549-2CEAMEAPEA

Pros and cons

5 positive · 2 caution
What owners get
High efficiency via SiC technology

SiC transistors at the MPPT/boost stage raise conversion efficiency from a typical ~96% (IGBT) to over 99% (max. 99.01%, European efficiency 98.70% per Hopewind datasheets), delivering a real lifetime energy yield gain.

8 independent MPPTs at 60A each

The 8x MPPT layout with up to 60A input current per tracker (V2.3 datasheet) enables flexible string configuration across varying orientations and shading, a meaningful edge over competitors with fewer MPPT channels on large ground-mount farms.

Wide operating range -25°C to 60°C

The inverter delivers full power up to 45°C ambient (40°C for the 385K variant), with an operating range of -25°C to +60°C plus IP66 and optional C5 anti-corrosion rating, supporting desert, coastal, and industrial sites without additional containerized cooling.

BNEF Tier 1 status and market recognition

Hopewind is listed as a Tier 1 manufacturer by Bloomberg New Energy Finance, and the 385kW unit was promoted as the world's most powerful utility-scale string inverter (per Solarbe Global), supporting bankability on project-financed markets.

SVG and weak-grid (SCR) support

Built-in SVG functionality and operation under low-SCR grid conditions improve connection stability for large ground-mount plants in regions with weaker grid infrastructure, an increasingly common DSO requirement.

Trade-offs
SiC not used across every power class

Despite SiC-centric marketing, a Hopewind representative confirmed models such as the 350kW unit use discrete IGBT devices, with SiC applied selectively based on cost-performance trade-offs - actual efficiency gains may vary between the 320/330/350/385K variants.

Limited track record outside China

Compared to established Tier 1 players (Huawei, Sungrow, SMA), Hopewind's global expansion is relatively recent (e.g., ranked 3rd in India in Q2 2026 per JMK Research with 12% share), meaning a shorter service history and smaller reference base for utility-scale installations in Europe.

Alternatives

All Hopewind inverters
Inverter Power Euro eff. MPPT Weight Difference
Hopewind HSHV385K-G01 385 kW 98.7% 8 142.0 kg You are here
HSHV385K-G02 385 kW 98.7% 8 155.0 kg 13.0 kg heavier
360 NX3 363 kW 98.6% 6 122.0 kg -22.0 kW, -2 MPPT, 20.0 kg lighter
400H2 360 kW 98.8% 14 150.0 kg -25.0 kW, +6 MPPT, 8.0 kg heavier
PSIT-350K-KH-UT 352 kW 98.8% - 124.0 kg -33.0 kW, 18.0 kg lighter
PSIT-350K-K-UT 352 kW 98.8% - 124.0 kg -33.0 kW, 18.0 kg lighter
SOFAR 350KTLX0 350 kW 98.8% - 113.0 kg -35.0 kW, 29.0 kg lighter
SG350HX 350 kW 98.8% 12 116.0 kg -35.0 kW, +4 MPPT, 26.0 kg lighter
X3-GRD-350K-HV 350 kW 98.8% 6 130.0 kg -35.0 kW, -2 MPPT, 12.0 kg lighter

About the HSHV-G01 series

6 answered

These answers cover the whole series. Where a figure differs, the specification above is this model's own.

Why does the HSHV320/330/350/385K-G01 series have as many as 8 independent MPPT trackers, and what are the benefits?
The inverter features 8 separate MPPT trackers, each rated for up to 60A, allowing strings with different tilt, orientation, or shading to be connected without reducing performance on the remaining circuits. In large utility-scale ground-mount farms with uneven terrain, this flexibility translates into higher real-world energy yield compared to inverters with fewer trackers.
What is the maximum efficiency of the Hopewind HSHV-G01 inverter and what drives it?
Thanks to SiC transistors, the inverter reaches a maximum efficiency of up to 99.01%. SiC technology reduces thermal and switching losses compared to conventional IGBT modules, lowering cooling requirements and extending the lifespan of power electronics components, even at full load.
Is the HSHV-G01 inverter suitable for desert or coastal installations?
Yes. The enclosure has an IP66 protection rating, and an optional C5 anti-corrosion class protects metal components against harsh environments such as salty coastal air or desert dust. The inverter maintains full output power at ambient temperatures up to 45°C, which is important in regions with high daytime temperatures.
What does SVG functionality and support for weak-grid (SCR) operation mean in this inverter?
SVG functionality allows the inverter to generate or absorb reactive power, stabilizing voltage at the point of common coupling. Support for operation in low short-circuit-ratio (weak grid/SCR) conditions enables connecting large PV farms even in locations with limited grid short-circuit capacity, without risk of unstable operation or tripping.
Can aluminum cables be used when connecting the HSHV-G01 inverter, and is it worth it?
Yes, the inverter is compatible with aluminum cables up to 400mm2 in cross-section. Aluminum cables are noticeably cheaper than copper at large cross-sections, which in utility-scale installations can significantly reduce AC wiring costs without compromising connection safety parameters.
What is the PID recovery function in the Hopewind inverter and why does it matter?
PID degradation is a loss of PV module power caused by voltage potential differences to ground, common in long strings with high voltage. The HSHV-G01 inverter includes a built-in PID recovery function and surge protection that minimize the risk of such degradation, helping maintain stable energy yield and a lower LCOE throughout the system's operating life.