Skip to main content

Deye SUN-100K-SG02HP3-US-EM6-277V

100 kW Hybrid Three-phase Battery-ready
Datasheet PDF
Rated AC (kW)
100.00
Strong · top 8%
Euro eff. (%)
98.1
Typical · median 98.2%
MPPT
6
Typical · median 4
Max DC (V)
1000
Typical · median 1100 V
Weight (kg)
-
Not published
Warranty (yrs)
5
Typical · median 5 yrs

The SUN-SG02HP3 series comprises industrial and commercial three-phase hybrid inverters from Deye, built for high-power installations that demand flexible energy management. What sets it apart is support for high-voltage lithium-ion battery storage, which helps reduce losses and simplifies wiring compared with low-voltage systems. The inverter features up to six independent MPPT trackers, making it well suited to handle partial shading and uneven irradiance across different strings of panels. A key advantage is the AC coupling function, which allows a battery storage system to be added to an existing solar installation without rebuilding it. The units can be paralleled up to ten pieces, in both on-grid and off-grid operation, and the system supports multiple battery banks running in parallel at the same time. Advanced logic lets installers schedule six charging and discharging periods per day, making it easier to optimize around tariffs and self-consumption. The inverter can also store energy generated by a diesel generator, making it a resilient choice for sites without stable grid power. This is a solution for integrators delivering large commercial and industrial projects, where scalability, reliability, and compliance with strict US market standards matter most.

Ranking

552 inverters from 30 to 100 kW
Metric This inverter Median Position in class Rank in class
European efficiency 98.1% 98.2% Typical 223
MPPT trackers 6 4 Typical 55
Max DC input voltage 1000 V 1100 V Typical 298
Weight per kW - 1.2 Not published -
Warranty 5 yrs 5 yrs Typical 45
Colour key Strong - top 25% Typical - middle 50% Weak - bottom 25%

Specifications

Open datasheet PDF
Rated AC power 100 kW Continuous output
Max apparent power 100.00 kVA
Phases Three-phase
Nominal AC voltage 277 V 0.88Un-1.1Un
Max AC current 120.4 A
Grid frequency 60 Hz Range 55-65Hz
Power factor 0.8 leading to 0.8 lagging
Harmonic distortion (THD) 3.0 %
Max DC input power 130.00 kW DC/AC ratio 1.30
Max DC voltage 1000 V Caps the string length
MPPT voltage range 150 to 850 V
Start-up voltage 180 V
MPPT trackers 6 2 strings each
Max input current per MPPT 36.0 A Must exceed the panel's Imp
Max short-circuit current per MPPT 54.0 A Must exceed the panel's Isc
European efficiency 98.1 % Weighted across part loads
Max efficiency 98.7 % Best single operating point
Battery port Yes
Battery voltage 160-1000V
Max charge current 160.0 A
Max discharge current 160.0 A
Backup power 100.00 kW Output during a grid outage
Grid-forming Yes
Dimensions 1061 × 621 × 338 mm Height × width × depth
Enclosure TYPE3R
Cooling forced-air
Noise 65 dB
Operating temperature -40 to 60 °C
Max humidity 100 %
Max altitude 3000 m
Interfaces Wi-FiDisplay
Protocols WIFIRS485CAN
Protection AFCIDC switchSurge protection
Warranty 5 years Standard manufacturer cover
Certifications UL 1741FCCIEEE 1547-2018IEEE 1547.1-2020UL 1699BUL 1998

Pros and cons

5 positive · 2 caution
What owners get
Native high-voltage battery support

A battery voltage range of roughly 160-1000 V (100K US model) allows direct operation with high-voltage lithium-ion storage without extra DC/DC converters, reducing wiring losses and costs compared to low-voltage 48 V systems.

Scalable parallel architecture

The 60-125 kW power classes (EM6/GM) can be connected in parallel up to 10 units, in both on-grid and off-grid modes, enabling commercial installations up to roughly 1.25 MW from a single hardware platform.

MPPT count scales with power class

The series scales its MPPT trackers from 3 (15-30 kW models) to 6-8 (60-125 kW models), allowing the configuration to match uneven string irradiance without oversizing the installation.

AC coupling and generator-charging backup

AC coupling allows adding a battery storage system to an existing PV installation without rebuilding it, while the ability to charge the battery from a diesel generator improves resilience for sites with unstable grid supply.

Compliance with US market standards

IEEE 1547-2018, IEEE 1547.1-2020, UL 1699B, and UL 1998 certifications confirmed in the 100K US datasheet open the door to US C&I projects where these standards are commonly required by utilities.

Trade-offs
Shorter standard warranty period

Base warranty is 5 years (extendable to 10 years for an additional fee), shorter than some tier-1 competitors in the C&I segment that offer 10 years standard at no extra cost.

Spec variance across power variants

MPPT count and string configuration differ significantly between power variants in the series (3 MPPTs for 15-30 kW vs. 6-8 MPPTs for 60-125 kW), requiring integrators to check the specific datasheet rather than relying on a general series description.

Alternatives

All Deye inverters
Inverter Power Euro eff. MPPT Weight Difference
Deye SUN-100K-SG02HP3-US-EM6-277V 100 kW 98.1% 6 - You are here
100M1-HYB 100 kW 98.4% - 108.0 kg +0.3 pp efficiency
100M1-HYA 100 kW 98.4% - 78.0 kg +0.3 pp efficiency
SUN-100K-SG02HP3-EU-GM8 100 kW 98.1% 10 161.7 kg +4 MPPT
SUN-100K-SG02HP3-EU-GM10 100 kW 98.1% 10 161.7 kg +4 MPPT
H3-100-Plus 100 kW 98.1% - 120.0 kg Similar on paper
P3-100-Plus 100 kW 98.1% - 120.0 kg Similar on paper
100TL 100 kW 98.1% - 80.0 kg Similar on paper
HYX-H100K-ET 100 kW 98.0% - 95.0 kg Similar on paper

About the SUN-SG02HP3 series

6 answered

These answers cover the whole series. Where a figure differs, the specification above is this model's own.

What is the maximum installation capacity when connecting multiple SUN-SG02HP3 inverters in parallel?
SUN-SG02HP3 series inverters can be connected in parallel up to ten units, allowing installations to reach power levels of hundreds of kilowatts depending on the selected model within the series. This configuration works in both grid-tied and off-grid modes, making it easy to scale the system as a commercial or industrial facility grows, without replacing already installed units.
Can multiple energy storage systems be connected to a SUN-SG02HP3 inverter at the same time?
Yes, the inverter design supports working with multiple battery storage systems in parallel, which matters in large commercial installations where the capacity of a single battery bank is often insufficient. The system automatically manages charging and discharging across the different storage units, maintaining voltage stability and balanced battery load.
What is the AC coupling function in the Deye SUN-SG02HP3 inverter, and is it worth using?
AC coupling allows an energy storage system to be added to an existing PV installation without modifying its DC side. It's worth using when a customer already has a working PV system and wants to add a battery without dismantling panels or rewiring the array. This approach significantly shortens installation time and reduces costs compared to a full system overhaul.
Why does the SUN-SG02HP3 support high-voltage battery storage instead of low-voltage systems?
Higher battery voltage allows the same power to be transmitted at lower current, reducing cable losses and enabling the use of thinner, cheaper cabling than in low-voltage systems. For commercial and industrial installations where power can reach dozens or hundreds of kilowatts, this has a real impact on efficiency and the overall cost of the investment.
Can the Deye SUN-SG02HP3 inverter handle partial shading of PV panels?
Yes, models in the SUN-SG02HP3 series feature up to six independent MPPT inputs, allowing separate control of different panel strings oriented in different directions or exposed to uneven sunlight. This means shading on part of the array, for example from a chimney or a neighboring building, doesn't significantly limit energy production from the remaining strings.
Can the SUN-SG02HP3 inverter work with a diesel generator when there's no grid power?
Yes, the unit can store energy coming from a generator, making it well suited to facilities without a stable grid connection, such as industrial sites with frequent power outages. This function allows the generator to be used for topping up the battery rather than only powering loads directly, improving fuel efficiency and backup reliability.