S6-GR3P-9K02-NV-ND
vs
SE15K (Delta grid version; part no. SExxK-xxxxxbxx4)
2 of 17 identical
Swap
Change inverters
Ginlong Solis S6-GR3P-9K02-NV-ND vs SolarEdge SE15K (Delta grid version; part no. SExxK-xxxxxbxx4)
VS

SolarEdge
SE15K (Delta grid version; part no. SExxK-xxxxxbxx4)
8.7 kW
97.6 % euro
Grid-tie
The verdict
S6-GR3P-9K02-NV-ND leads on the differences that matter
The largest is rated ac power: 0.30 kW apart. 2 of 17 comparable parameters are identical, with 15 more left out because at least one datasheet does not publish them.
See all 15 differencesHow alike are they
2
of 17 comparable
parameters are identical
parameters are identical
identical
differs
not published
01
15 of 17 parameters
What actually differs
Parameter
S6-GR3P-9K02-NV-ND
SE15K (Delta grid version; part no. SExxK-xxxxxbxx4)
Difference
Rated AC power
9.00 kW
8.70 kW
0.30 kW apart
Max DC voltage
1100 V
600 V
500 V apart
Max AC power
9.00 kW
8.70 kW
0.30 kW apart
Max PV power
13.50 kW
11.74 kW
1.76 kW apart
Weight
15.4 kg
30.7 kg
15.3 kg lighter
Weight per kW
1.7 kg/kW
3.5 kg/kW
1.8 kg/kW lighter
Noise
30 dB
50 dB
20 dB quieter
European efficiency
97.9 %
97.6 %
0.3 pp more efficient
Max efficiency
98.5 %
98.0 %
0.5 pp more efficient
DC/AC ratio
1.50
1.35
0.15 more oversizing headroom
Max AC current
13.7 A
23.0 A
9.3 A apart
Ingress protection
IP66
IP65
IP66 vs IP65
MPPT voltage range
160-1000 V
370-600 V
160-1000 V vs 370-600 V
Dimensions
410x355x179 mm
540x315x260 mm
410x355x179 mm vs 540x315x260 mm
Cooling
natural
forced-air
natural vs forced-air
02
Full specification
Parameter
S6-GR3P-9K02-NV-ND
SE15K (Delta grid version; part no. SExxK-xxxxxbxx4)
Difference
AC output
Rated AC power
9.00 kW
8.70 kW
0.30 kW apart
Max AC power
9.00 kW
8.70 kW
0.30 kW apart
Grid connection
3-phase
3-phase
Same
Nominal AC voltage
-
230 V
Not published by Ginlong Solis
Max AC current
13.7 A
23.0 A
9.3 A apart
PV input
Max PV power
13.50 kW
11.74 kW
1.76 kW apart
DC/AC ratio
1.50
1.35
+0.15 for S6-GR3P-9K02-NV-ND
Max DC voltage
1100 V
600 V
500 V apart
MPPT voltage range
160-1000 V
370-600 V
160-1000 V vs 370-600 V
Start voltage
160 V
-
Not published by SolarEdge
MPP trackers
2
-
Not published by SolarEdge
Strings per tracker
1
-
Not published by SolarEdge
Max input current per tracker
21.0 A
-
Not published by SolarEdge
Efficiency
European efficiency
97.9 %
97.6 %
+0.3 pp for S6-GR3P-9K02-NV-ND
Max efficiency
98.5 %
98.0 %
+0.5 pp for S6-GR3P-9K02-NV-ND
CEC efficiency
-
-
Neither datasheet publishes this
Battery
Battery input
-
-
Neither datasheet publishes this
Battery voltage
-
-
Neither datasheet publishes this
Max charge current
-
-
Neither datasheet publishes this
Backup power
-
-
Neither datasheet publishes this
Physical
Weight
15.4 kg
30.7 kg
-15.3 kg for S6-GR3P-9K02-NV-ND
Weight per kW
1.7 kg/kW
3.5 kg/kW
-1.8 kg/kW for S6-GR3P-9K02-NV-ND
Dimensions
410x355x179 mm
540x315x260 mm
410x355x179 mm vs 540x315x260 mm
Ingress protection
IP66
IP65
IP66 vs IP65
Cooling
natural
forced-air
natural vs forced-air
Noise
30 dB
50 dB
-20 dB for S6-GR3P-9K02-NV-ND
Max operating temperature
60 °C
60 °C
Same
Connectivity and safety
Wi-Fi
-
Yes
Not published by Ginlong Solis
Ethernet
-
Yes
Not published by Ginlong Solis
Arc fault protection
-
Yes
Not published by Ginlong Solis
Integrated DC switch
Yes
-
Not published by SolarEdge
Warranty
Warranty
-
-
Neither datasheet publishes this
03
Open all inverters
More useful comparisons
Same type, similar size
Growatt
Ginlong Solis S6-GR3P-9K02-NV-ND vs Growatt MOD 9000TL3-X
6 differences, the largest is max input current per tracker
Same type, similar size
Ginlong Solis
Ginlong Solis S6-GR3P-9K02-NV-ND vs Solis-3P9K-4G
12 differences, the largest is max dc voltage
Same type, similar size
Growatt
Ginlong Solis S6-GR3P-9K02-NV-ND vs Growatt MIN 9000TL-X
11 differences, the largest is max dc voltage
Same type, similar size
GoodWe
SolarEdge SE15K (Delta grid version; part no. SExxK-xxxxxbxx4) vs GoodWe GW8500-MS
11 differences, the largest is rated ac power
04
Written summary
Checking cache...
Every figure here is from the manufacturers' own datasheets - a dash means the value is not published, never an estimate.