title: "SMA Solar STPS60-10 Hybrid Inverter: Specs & Datasheet | ComparePV"
description: "SMA Solar STPS60-10 75 kW hybrid inverter. Specs: 1000 V max DC input, 77.0 kg, 5 yrs warranty."
source: "https://comparepv.com/inverter/sma-solar-stps60-10"
updated: 2026-11-14
---

# SMA Solar STPS60-10


## Identity

- **Manufacturer:** SMA Solar
- **Model:** STPS60-10
- **Series:** Sunny Tripower Storage 60
- **Rated AC power:** 75 kW
- **Type:** Hybrid
- **Phases:** Three-phase
- **Battery port:** yes


## How it compares

Compared against 676 inverters from 30 to 100 kW. Ranks are within that class.


| Measure | This inverter | Class median | Standing | Rank in class |
| --- | --- | --- | --- | --- |
| European efficiency | - | 98.2% |  |  |
| MPPT trackers | - | 4 |  |  |
| Max DC input voltage | 1000 V | 1100 V | Typical | 375 |
| Weight per kW | 1.0 | 1.2 | Typical | 248 |
| Warranty | 5 yrs | 5 yrs | Typical | 45 |


## Specification


### AC output

- **Rated AC power:** 75 kW
- **Max apparent power:** 75.00 kVA
- **Phases:** Three-phase
- **Nominal AC voltage:** 400 V
- **Max AC current:** 109.0 A
- **Grid frequency:** 50 Hz
- **Power factor:** 0 overexcited to 0 underexcited
- **Harmonic distortion (THD):** 1.0 %


### PV input

- **Max DC input power:** 60.00 kW
- **Max DC voltage:** 1000 V
- **MPPT voltage range:** 575 to 1000 V
- **Max input current per MPPT:** 140.0 A


### Efficiency

- **Max efficiency:** 98.8 %


### Battery

- **Battery port:** Yes
- **Battery voltage:** 575 V to 1000 V
- **Max charge current:** 140.0 A
- **Max discharge current:** 140.0 A


### Physical

- **Dimensions:** 740 × 570 × 306 mm
- **Weight:** 77.0 kg
- **Enclosure:** IP65
- **Cooling:** forced-air
- **Noise:** 58 dB
- **Operating temperature:** -25 to 60 °C
- **Max humidity:** 95 %


### Connectivity and protection

- **Interfaces:** Ethernet, Display
- **Protocols:** RS485, Modbus RTU, Modbus TCP, SunSpec Alliance, Ethernet
- **Protection:** DC switch, Surge protection


### Warranty and certificates

- **Warranty:** 5 years
- **Certifications:** C10/11:2019, EN 50438:2013, EN 50549-1/-2:2019, G99/1-3:2018, G99-NI:2019, IEC 62116, IEC 61727, IEC 62109-1/-2, NA-EEA-NE7 CH 2020, NRS 097-2-1:2017, PN-EN 50549-1/2, TOR Erzeuger Typ A:2019, UTE C 15-712-1, VDE-AR-N 4105:2018-11, VDE-AR-N 4110:2018-11, VDE 0126-1-1/A1, VFR 2019, UL 508, UL 60950-1, CSA C22.2 No. 60950-1-07, EN 60950-1, EN 55022 Class A, EN 61000-3-2 Class D, EN 61000-3-3, EN 61000-6-4, EN 55024, FCC Part 15, Sub-part B Class A


### Pros

- **AC-coupled architecture** - The battery storage connects on the AC side (75 kVA, 400 V) without requiring any rework of the existing PV installation's DC side - this shortens integration time and lowers retrofit costs for C&I sites compared with DC-coupled solutions.
- **Four-quadrant operation and reactive power control** - A fully adjustable power factor (from 0 overexcited to 0 underexcited) enables active grid stabilization support, which is becoming a mandatory requirement from an increasing number of DSOs for industrial grid connections.
- **Modular scalability up to the MW range** - A single unit delivers up to 75 kVA output power and up to 60 kW of DC battery charging power, and with the SMA inverter manager, installations can be scaled in parallel up to megawatt range without changing the control platform.
- **Low nighttime self-consumption** - Standby power draw is below 3 W, which translates into meaningfully lower daily energy losses in commercial installations running many units in parallel.
- **Manufacturer track record and build quality** - SMA Solar, founded in Germany in 1981, is one of the longest-standing inverter manufacturers on the market, reflected in its refined transformerless design with active cooling and an outdoor-rated enclosure for a wide temperature range.


### Cons

- **Narrow DC battery voltage window** - The permissible DC voltage range is 575-1000 V, which limits compatibility with some low-voltage storage systems and requires selecting a battery matched to this specific voltage window at the design stage.
- **Dependence on Modbus and the SMA ecosystem** - Full EMS integration requires the standard Modbus protocol and the SMA inverter manager, which in complex, multi-vendor storage systems may demand extra integration work compared with more universal interfaces.


## About this series

The Sunny Tripower Storage 60 is an industrial-grade battery inverter built for commercial and industrial energy storage projects, engineered to work with high-voltage lithium-ion battery systems. Its standout advantage is its **AC-coupled architecture**, which allows a battery storage system to be added to an existing solar PV installation without reworking the DC side, dramatically cutting deployment time and cost for commercial and industrial sites. The unit also features **four-quadrant operation**, actively contributing to reactive power regulation and grid stabilization, an increasingly important requirement from grid operators. The inverter is fully **modular and scalable up to the megawatt range**, making it well suited to projects where storage capacity needs to grow alongside PV expansion or rising plant demand. Standard Modbus-based communication and integration with the SMA Inverter Manager simplify deployment within complex energy management systems (EMS). Thanks to its **transformerless design with active cooling** and a weatherproof enclosure, the unit is suitable for outdoor installation across a wide temperature range. This is a solution built for energy storage integrators, PV plant operators, and industrial facilities seeking a flexible, resilient platform for energy management.


## Questions


### What is the maximum charge/discharge power supported by the Sunny Tripower Storage 60 inverter?

The Sunny Tripower Storage 60 supports battery charging and discharging with a maximum DC power of up to 60 kW, within a battery voltage range of 575-1000 V and a maximum DC current of 140 A. On the AC side, the maximum output current is 109 A at 400 V / 50 Hz. Thanks to its modular architecture, multiple units can be connected in parallel to build installations up to the megawatt range.


### How does the AC-coupled architecture of the Sunny Tripower Storage 60 differ from DC-coupled systems?

In an AC-coupled architecture, the energy storage system is connected on the AC side of the installation, independently from the existing PV inverter. This means no DC wiring rework or panel reconfiguration is needed, which significantly shortens deployment time and reduces production downtime in commercial and industrial sites compared to DC-coupled systems that require integration on a shared DC bus.


### Can the Sunny Tripower Storage 60 be installed outdoors?

Yes, the inverter has a transformerless design with active cooling and an IP65 (NEMA 3R) rated enclosure, allowing outdoor installation. It operates in a temperature range of -25°C to +60°C, making it suitable for demanding weather conditions in both cold and hot climates, without requiring a dedicated technical room.


### Which batteries are compatible with the Sunny Tripower Storage 60?

The inverter is specifically designed to work with high-voltage lithium-ion batteries, within a DC voltage range of 575 to 1000 V. Communication with the battery's BMS runs over the standard Modbus protocol, simplifying integration with various battery storage models available on the market without the need for custom communication adapters.


### Does the Sunny Tripower Storage 60 support reactive power control and grid stabilization?

Yes, the unit operates in four-quadrant mode, actively participating in reactive power regulation and grid stabilization. This capability is increasingly important given the requirements imposed by distribution system operators (DSOs) on large energy storage installations, which must actively respond to fluctuations in grid parameters.


### How many storage units can be combined into one system based on the Sunny Tripower Storage 60?

The inverter is fully modular and scalable, allowing multiple units to be connected in parallel and the installation to be expanded up to the megawatt range. Managing a larger fleet of inverters is simplified through integration with the SMA Inverter Manager, which coordinates the entire system within a single overarching energy management system (EMS), a key advantage for growing industrial installations.


## Datasheet

[Manufacturer datasheet (PDF)](https://comparepv.com/datasheets/inverters/STPS60-DS-en-31-64cd59c4b028.pdf)


## Alternatives


| Inverter | Rated AC | Euro efficiency | MPPT | Weight | Difference |
| --- | --- | --- | --- | --- | --- |
| [Deye SUN-75K-SG02HP3-EU-EM6](https://comparepv.com/inverter/deye-sun-75k-sg02hp3-eu-em6) | 75 kW | 98.1% | 6 | 105.0 kg | 28.0 kg heavier |
| [HYXiPower HYX-H75K-ET](https://comparepv.com/inverter/hyxipower-hyx-h75k-et) | 75 kW | 98.0% |  | 95.0 kg | 18.0 kg heavier |
| [GoodWe GW75KETR-G10](https://comparepv.com/inverter/goodwe-gw75ketr-g10) | 75 kW | 97.7% |  | 82.0 kg | 5.0 kg heavier |
| [GoodWe GW75K-ET-G10](https://comparepv.com/inverter/goodwe-gw75k-et-g10) | 75 kW | 97.7% | 8 | 97.0 kg | 20.0 kg heavier |
| [SAJ CH3-75K-T6](https://comparepv.com/inverter/saj-ch3-75k-t6) | 75 kW | 97.5% | 2 | 145.0 kg | 68.0 kg heavier |
| [GoodWe GW75KETR-L-G10](https://comparepv.com/inverter/goodwe-gw75ketr-l-g10) | 75 kW | 96.8% |  | 98.0 kg | 21.0 kg heavier |
| [Ginlong Solis S6-EH3P75K10-LV-YD-H](https://comparepv.com/inverter/ginlong-solis-s6-eh3p75k10-lv-yd-h) | 75 kW | 94.6% | 10 | 170.0 kg | 93.0 kg heavier |
| [Growatt WIT 75K-A-US / WIT 75K-AU-US](https://comparepv.com/inverter/growatt-wit-75k-a-us-wit-75k-au-us) | 75 kW |  |  | 120.0 kg | 43.0 kg heavier |


---

Source: https://comparepv.com/inverter/sma-solar-stps60-10